EFFET D'UNE CHARGE INAPPROPRIEE EN FRIGORIGENE SUR LA PERFORMANCE D'UN CONDITIONNEUR D'AIR AVEC DETENTE PAR TUBE CAPILLAIRE.

THE EFFECT OF IMPROPER REFRIGERANT CHARGING ON THE PERFORMANCE OF AN AIR CONDITIONER WITH CAPILLARY TUBE EXPANSION.

Auteurs : O'NEAL D. L., FARZAD M.

Type d'article : Article

Résumé

ON DECRIT UNE RECHERCHE ENTREPRISE POUR QUANTIFIER L'EFFET D'UNE CHARGE INAPPROPRIEE EN FRIGORIGENE SUR LA PERFORMANCE EN REGIME STABLE ET SAISONNIERE D'UN CONDITIONNEUR D'AIR RESIDENTIEL A DEUX BLOCS. ON A PASSE EN REVUE LA BIBLIOGRAPHIE, CONSTRUIT UNE INSTALLATION EXPERIMENTALE ET RECUEILLI PUIS ANALYSE DES DONNEES. UN CONDITIONNEUR D'AIR A DEUX BLOCS D'UNE PUISSANCE FRIGORIFIQUE DE 10,6 KILOWATTS, AVEC DETENTE PAR TUBE CAPILLAIRE, A ETE UTILISE POUR LES EXPERIENCES. ON A FAIT SYSTEMATIQUEMENT VARIER LA CHARGE DANS LE SYSTEME, AFIN DE DETERMINER SON EFFET SUR LES VARIABLES DU SYSTEME : LA PUISSANCE, LA CONSOMMATION D'ELECTRICITE, LE COP ET LE COP SAISONNIER. ON A OBSERVE QUE LA MOINDRE INSUFFISANCE DE CHARGE, MEME DE 5 %, POUVAIT FAIRE CHUTER JUSQU'A 6,1 % LE COP SAISONNIER. (INT. BUILD. SERV. ABSTR., GB., 25, N 6, 1990/11-12, 90-01748.

Détails

  • Titre original : THE EFFECT OF IMPROPER REFRIGERANT CHARGING ON THE PERFORMANCE OF AN AIR CONDITIONER WITH CAPILLARY TUBE EXPANSION.
  • Identifiant de la fiche : 1991-2239
  • Langues : Anglais
  • Source : Energy Build. - vol. 14 - n. 4
  • Date d'édition : 1990
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.