Document IIF

Méthodologies améliorées dans la simulation des systèmes de conditionnement d'air utilisés sous des conditions non prévues lors de la conception.

Improved methodologies for simulating unitary air conditioners at off-design conditions.

Auteurs : SHEN B., BRAUN J. E., GROLL E. A.

Type d'article : Article, Article de la RIF

Résumé

Models for unitary air conditioners and heat pumps typically have difficulties in providing accurate predictions for the following situations: 1) charge modelling over a large range of charge levels; 2) two-phase refrigerant entering fixed-orifice expansion devices; 3) two-phase refrigerant entering compressors; and 4) non-uniform refrigerant mass flow allocation among evaporator circuits at low indoor air flow rates. This paper gives descriptions and assessments of improved modelling methodologies for all four issues. The study utilizes data obtained from extensive testing at a wide range of operating conditions for two R410A units and one R407C unit.

Documents disponibles

Format PDF

Pages : pp. 1837-1849

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Improved methodologies for simulating unitary air conditioners at off-design conditions.
  • Identifiant de la fiche : 2009-2112
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 7
  • Date d'édition : 11/2009

Liens


Voir d'autres articles du même numéro (33)
Voir la source