Document IIF

Effet de la conduction de la chaleur par le biais des ailettes d'un refroidisseur à gaz en serpentin à microcanaux, dans un système au CO2 transcritique.

Effect of heat conduction through the fins of a microchannel serpentine gas cooler of transcritical CO2 system.

Auteurs : PARK C. Y., HRNJAK P.

Type d'article : Article, Article de la RIF

Résumé

This paper presents results of an experimental study to investigate the effect of conduction through the fins on the capacity of a serpentine gas cooler. The gas cooler was a part of a transcritical CO2 system which was operated in A/C mode. The capacity of the gas cooler was carefully measured in the chamber which simulated the outdoor condition with the original heat exchanger. In order to experimentally validate the conduction effect on the capacity, some sections of the fins, where the conduction was most significant, were cut by EDM (Electrical Discharge Machining). The capacity of the heat exchanger, after cutting fins, was measured in the same chamber at nearly identical test conditions as before cutting. Gas cooler capacity was improved up to 3.9% by cutting the fins, and temperature difference between refrigerant exit and air inlet for the gas cooler was reduced by 0.9-1.5°C. The maximum uncertainty in the capacity measurements was 2.5% and the accuracy of temperature measurements was 0.1°C. It was shown by system simulation that system COP could be improved by 5% by eliminating this severe conduction effect, as was done in this experiment. The tube surface temperature at some points of the gas cooler was measured and infrared images were taken to show the conduction effect before and after cutting fins.

Documents disponibles

Format PDF

Pages : 389-397

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Effect of heat conduction through the fins of a microchannel serpentine gas cooler of transcritical CO2 system.
  • Identifiant de la fiche : 2007-0602
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 3
  • Date d'édition : 05/2007

Liens


Voir d'autres articles du même numéro (16)