Document IIF

Effets des échangeurs de chaleur supplémentaires sur le COP d'un réfrigérateur à absorption à LiBr-eau à double effet.

Effects of additional heat exchangers on the COP of a double effect LiBr-water absorption refrigerator.

Auteurs : JEONG S. Y., LEE S. W.

Résumé

Because of soaring energy prices, lots of efforts have been done to improve the COP of double effect Libr-water absorption chillers. This paper demonstrates how the COP of a double effect absorption refrigeration cycle is influenced by additional heat exchangers such as an ESX (exhaust gas to solution heat exchanger), an RSX (refrigerant to solution heat exchanger) and an SCA (solution cooled absorber). Using EES (engineering Equation Solver), the effect of the UA-values of the additional components on the system COP is calculated, and the proper UA-values are suggested regarding both the COP and the initial cost of the product.

Documents disponibles

Format PDF

Pages : ICR07-B1-1278

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Effects of additional heat exchangers on the COP of a double effect LiBr-water absorption refrigerator.
  • Identifiant de la fiche : 2008-0186
  • Langues : Anglais
  • Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Date d'édition : 21/08/2007

Liens


Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence