Document IIF
Efficacité d'un rideau d'air bi- et tridimensionnels utilisé pour limiter l'infiltration d'air d'une chambre froide : modèles utilisant la dynamique numérique des fluides.
Two and three dimensional CFD models of the effectiveness of an air curtain used to restrict cold room infiltration.
Auteurs : FOSTER A. M., SWAIN M. J., JAMES S. J.
Résumé
The aim of this study was to compare the measured effectiveness of an air curtain device at different jet velocities against predictions from 2D and 3D computational fluid dynamics (CFD) models. The predicted maximum effectiveness of the air curtain was 0.13 higher than measured for the 2D model and 0.05 lower than measured for the 2D model. The 2D model under predicted the optimum jet velocity by 7.5 m/s, the 3D model over predicted it by 4 m/s. CFD has shown that the flow from this air curtain cannot be considered as 2D. The central part of the jet is deflected away from the cold store by the Coanda effect caused by the air curtain device's fan body. The edges of the jet are deflected into the cold store by the stack pressures and turn into the void caused by the deflected central jet.
Documents disponibles
Format PDF
Pages : ICR07-D1-1238
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Two and three dimensional CFD models of the effectiveness of an air curtain used to restrict cold room infiltration.
- Identifiant de la fiche : 2008-0295
- Langues : Anglais
- Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Date d'édition : 21/08/2007
Liens
Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence
Indexation
- Thèmes : Entrepôts frigorifiques : conception, construction, isolation et équipement
- Mots-clés : Vitesse (fluides); Jet; Chambre froide; CFD; Rideau d'air; Rendement; Air
-
Flow regimes and thermal patterns in cold rooms.
- Auteurs : ABOU ZIED A., EL-HARRIRY G., KHALIL E. E.
- Date : 16/06/2013
- Langues : Anglais
- Source : Clima 2013. 11th REHVA World Congress and 8th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings.
- Formats : PDF
Voir la fiche
-
Air infiltration into walk-in cold rooms throug...
- Auteurs : CLELAND D. J., EAST A. R., JEFFERY P. B.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche
-
A NEW VERTICAL AIR CURTAIN DESIGN FOR COLD STORES.
- Auteurs : MALE J. van
- Date : 07/08/1983
- Langues : Anglais
- Source : [Refrigeration serving humanity]. Proceedings of the XVIth international Congress of Refrigeration.
- Formats : PDF
Voir la fiche
-
INFILTRATION OF AIR INTO COLD STORES.
- Auteurs : PHAM Q. T., OLIVER D. W.
- Date : 07/08/1983
- Langues : Anglais
- Source : [Refrigeration serving humanity]. Proceedings of the XVIth international Congress of Refrigeration.
- Formats : PDF
Voir la fiche
-
AIR INTERCHANGE RATE THROUGH A COLD STORE OPEN ...
- Auteurs : MORENO J.
- Date : 24/08/1987
- Langues : Anglais
- Source : Development in refrigeration, refrigeration for development. Proceedings of the XVIIth international Congress of Refrigeration.