ESSAI SUR LA PERFORMANCE D'UN SYSTEME DE POMPE A CHALEUR A DETENTE DIRECTE.

PERFORMANCE TEST OF A DIRECT EXPANSION HEAT PUMP SYSTEM.

Auteurs : EDWARDS J. A.

Résumé

ON DONNE LES RESULTATS POUR UNSYSTEME DE POMPE A CHALEUR A DETENTE DIRECTE RELIE AU SOL DE FACON ORIGINALE PAR UN CONCENTRATEUR DE TRANSFERT DE CHALEUR. LE SYSTEME REDUIT PLUSIEURS DES RESISTANCES THERMIQUES LIEES AUX TRAJETS D'ECOULEMENT DE LA CHALEUR DANS D'AUTRES TYPES DE SYSTEMES DE POMPES A CHALEUR RELIEES AU SOL. ON DONNE LES RESULTATS DE PERFORMANCE DE CE SYSTEME POUR LES OPERATIONS DE REFRIGERATION ET DE CHAUFFAGE SUR UNE PERIODE D'ESSAI DE 1 AN. ON LES COMPARE AUX RESULTATS EXPERIMENTAUX OBTENUS POUR D'AUTRES TYPES DE CONFIGURATION ENTERREE (TUYAU HORIZONTAL ENTERRE, LIT CAILLOUTEUX, CITERNE INSTALLEE A LA SURFACE DU SOL ET PUITS VERTICAL A BOUCLE FERMEE) ET D'UNE POMPE A CHALEUR OU L'AIR ES L SCEEHLEA LE COP CORRESPONDANT A LA PERIODE DE CHAUFFAGE ETAIT DE 4,2 ET CELUI CORRESPONDANT A LA PERIODE DE REFROIDISSEMENT DE 3,1. PAR RAPPORT AUX AUTRES POMPES A CHALEUR ESSAYEES, IL S'AGIT D'UNE AMELIORATION DE LA PERFORMANCE DE 7 A 50 %.

Détails

  • Titre original : PERFORMANCE TEST OF A DIRECT EXPANSION HEAT PUMP SYSTEM.
  • Identifiant de la fiche : 1989-1567
  • Langues : Anglais
  • Date d'édition : 1988
  • Source : Source : ASHRAE Trans.
    vol. 94; n. 1; 318-329; 13 fig.; 4 ref.; discuss.