ESSAIS IN SITU SUR LA CORROSION DES MATERIAUX DES ECHANGEURS DE CHALEUR ENTERRES, DANS LA STATION EXPERIMENTALE DE SCHWALBACH COMPORTANT DES POMPES A CHALEUR COUPLEES AU SOL.

IN-SITU CORROSION TEST FOR GROUND HEAT EXCHANGER MATERIALS IN SCHWALBACH GROUND COUPLED HEAT PUMP RESEARCH STATION.

Auteurs : SANNER B., KNOBLICH K.

Type d'article : Article

Résumé

DE 1985 A 1989, A WETZLAR, ALLEMAGNE, ON A MIS EN SERVICE UNE INSTALLATION EXPERIMENTALE DE RECHERCHE ET DEVELOPPEMENT, COMPRENANT DES POMPES A CHALEUR COUPLEES AU SOL AVEC DES ECHANGEURS DE CHALEUR VERTICAUX ENTERRES. AU COURS DES ESSAIS D'EXTRACTION DE CHALEUR, EFFECTUES DE 1986 A 1988, 12 ECHANTILLONS DE 5 MATERIAUX DIFFERENTS ONT ETE EXPOSES A DE L'EAU SOUTERRAINE DANS UN PUITS D'UNE PROFONDEUR DE 50 M. DANS L'ARTICLE, ON TRAITE DE LA PERTE DE MASSE DUE A LA CORROSION, AINSI QUE DE LA CHIMIE DE L'EAU SOUTERRAINE. LA RECHERCHE MONTRE QUE LE FER PUR, LORSQU'IL EST EN CONTACT AVEC DE L'EAU SOUTERRAINE, PERD LA MOITIEDE SA MASSE SUR UNE PERIODE DE 30 ANS ENVIRON. SEULS L'ACIER INOXYDABLE OU LE PLASTIQUE (COMME LE POLYETHYLENE DE HAUTE DENSITE) SONT SUFFISAMMENT DURABLES POUR ETRE UTILISES DANS LES ECHANGEURS DE CHALEUR ENTERRES.

Détails

  • Titre original : IN-SITU CORROSION TEST FOR GROUND HEAT EXCHANGER MATERIALS IN SCHWALBACH GROUND COUPLED HEAT PUMP RESEARCH STATION.
  • Identifiant de la fiche : 1992-1373
  • Langues : Anglais
  • Source : IEA HPC Newsl. - vol. 9 - n. 3
  • Date d'édition : 09/1991
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (5)
Voir la source