Document IIF

Estimation généralisée du COP des processus à pompe à chaleur fonctionnant hors conception.

Generalized COP estimation of heat pump processes for operation off the design point of equipment.

Numéro : pap. n. 648

Auteurs : OMMEN T., JENSEN J., MEESENBURG W., et al.

Résumé

Heat pumps (HPs) and their individual components experience a significant share of operation away from the design point, due to both sink and source temperature variations as well as operation at part load. In the present study, we expand a generalized HP COP estimation for design conditions to include the performance of conditions within the typical limits for the operating range. The estimation was compared to results based on detailed thermodynamic models of two representative HP installations, of different size and design temperatures. The considered configurations include a 14 kW R134a one-stage cycle and an 800 kW two-stage ammonia heat pump. Based on the design point COP estimation, and five linearized off-design contributions, the performance estimation of COP showed a maximum deviation of 8 %.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Generalized COP estimation of heat pump processes for operation off the design point of equipment.
  • Identifiant de la fiche : 30026015
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.0648