Étude d'une méthode permettant de réduire la température de refoulement d'un système frigorifique au R32.

[In Chinese. / En chinois.]

Auteurs : QIN Y., ZHANG J.

Type d'article : Article

Résumé

The paper analyzes theoretically the change of refrigerant system after replacement of R410 with R32. Such replacement led to the increase of the discharge temperature of the system. The method of gas refrigerant injection was proposed to reduce the discharge temperature. Some experiments were made to investigate the variation of refrigerant system on charging rate, capacity, COP, discharge temperature after the replacement of R410A with R32. The results showed that, comparing with R410a system, the capacity, COP and discharge temperature of R32 were increased, and the R32 system with gas refrigerant injection can reduce effectively the discharge temperature, and increase the capacity and COP. It can be concluded that R32 is a promising refrigerant candidate, and the limitation brought by high discharge temperature of R32 can be broken with the gas refrigerant injection system.

Documents disponibles

Format PDF

Pages : 14-17

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30004182
  • Langues : Chinois
  • Source : Journal of Refrigeration - vol. 33 - n. 143
  • Date d'édition : 02/2012

Liens


Voir d'autres articles du même numéro (11)
Voir la source