Étude de l'application d'une unité d'échangeur de chaleur de caloduc à boucle et entrainement par pompe pour un petit centre de données.

Application investigation on a pumped loop heat pipe heat exchanger unit for a small data center.

Numéro : pap. n. 175

Auteurs : WEI C., MA G., ZHOU F., et al.

Résumé

The pumped loop heat pipe heat exchanger unit for cooling consumes low power and has a high coefficient of performance (EER). For optimization applications at small data centers, this paper investigated the operating performance of the pumped loop heat pipe heat exchanger unit used in a small data center. The EER under different outdoor temperatures was analyzed, and the fitted operating characteristic curve showed that EER varied with outdoor temperature. An energy saving analysis was done with the fitting curve, and the total energy consumption was calculated at each temperature interval in Beijing. The results show that in transitional and winter season, when the outdoor temperature is below 15°C, the pumped loop heat pipe heat exchanger unit can be turned on to bear part or total thermal load and performs well in energy saving. Compared to the air conditioning and refrigeration system for cooling, the energy saving can reach at least 35.76%.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Application investigation on a pumped loop heat pipe heat exchanger unit for a small data center.
  • Identifiant de la fiche : 30015342
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0175

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence