Étude expérimentale d'un système de refroidissement à rayonnement.

[In Chinese. / En chinois.]

Auteurs : CHENG Y., ZUO R.

Type d'article : Article

Résumé

The radiation cooling is experimentally studied wi th air as the cooling medium. polyester (PET) as radiative material and low-density polyethylEne (LDPE) film as transparent cover. The experimental results with horizontal device indicate that the maximum temperature difference between PET and the environment is 9.9°C, and that between internal air and the environment is 7.2°C. In the same climatic condition for the device tilted, the results for 45° tilt angle are the best, the maximum temperature difference between internal air and the environment is 7.6°C. In the air flow experiment, the maximum temperature difference is obta ined at wind speed of 0.6m/s~0.8m/s, the temperature difference between the outlet and environment is 5.2°C, and the stable temperature difference is obtained throughout the night. By calculation, the effective cooling power of the device is 73.6 W/m2.

Documents disponibles

Format PDF

Pages : 48-52

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30003125
  • Langues : Chinois
  • Source : Journal of Refrigeration - n. 140
  • Date d'édition : 08/2011

Liens


Voir d'autres articles du même numéro (13)
Voir la source