Étude expérimentale de l'état de l'aspiration du frigorigène et de la température de refoulement pour un compresseur à piston roulant.

[In Chinese. / En chinois.]

Auteurs : YANG L., TAO L., TAO H., et al.

Type d'article : Article

Résumé

Influence of suction refrigerant state on system performance and discharge temperature was carried out through a variable speed
rolling piston compressor test bench. Results show that under the most air-conditioning conditions and the most operating frequencies, system capacity and COP will reach peak value, and discharge temperature will be effectively decreased to the corresponding theoretical discharge temperature of isentropic compression process when suction vapor quality is about 0. 95 - 0.98. Considering running safety, the appropriate suction vapor quality should be among 0.95 - 0.98.

Documents disponibles

Format PDF

Pages : 49-53, 86

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails


Liens


Voir d'autres articles du même numéro (13)
Voir la source