Document IIF
Étude expérimentale du phénomène de sifflement dans le détendeur électronique d'un système de conditionnement d'air multi-split.
Experimental study on whistling noise behavior in electronic expansion valve of multi-split air conditioning system.
Résumé
A sharp whistling noise occurs during the refrigerant throttling process in electronic expansion valves (EEVs) of a multi-split air conditioning system, which deteriorates comfortability. The purpose of this paper is to study the whistling noise mechanism and to quantitatively investigate the effects of refrigerant throttling velocity and EEV opening on the noise frequency and sound pressure level (SPL). The experimental conditions cover the throttling velocity ranging from 1.5 – 5 m s-1, and the EEV opening ranging from 35% – 75%. The results show that the whistling noise comes from the pressure disturbance caused by the periodic shedding vortices. High refrigerant throttling velocity facilitates the whistling noise frequency which increased by 74% as the throttling velocity increased. Low EEV opening helps to reduce the whistling noise SPL which decreased by 10.5% as the EEV opening decreased. Improving the resonant frequency of the EEV chamber can help to eliminate the whistling noise.
Documents disponibles
Format PDF
Pages : 12
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Experimental study on whistling noise behavior in electronic expansion valve of multi-split air conditioning system.
- Identifiant de la fiche : 30031481
- Langues : Anglais
- Sujet : Technologie
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Date d'édition : 21/08/2023
- DOI : http://dx.doi.org/10.18462/iir.icr.2023.0079
Liens
Voir d'autres communications du même compte rendu (491)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Conditionnement d'air pour le confort;
Systèmes de détente - Mots-clés : Experimentation; Système split; Bruit; Détendeur électronique; Banc d'essai; Fréquence
-
Effects of electronic expansion valve tube arra...
- Auteurs : ZHOU S., ZHAN F., ZHU T., DING G., LIU H., CHEN W., CHEN H.
- Date : 05/2024
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 161
- Formats : PDF
Voir la fiche
-
Experimental investigation on two-phase flow no...
- Auteurs : ZHOU S., ZHANG F., DING G.
- Date : 02/2023
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 146
- Formats : PDF
Voir la fiche
-
Experimental study on the failure of electronic...
- Auteurs : LI J., DU Y., WU J., LIN J., WANG C.
- Date : 04/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 112
- Formats : PDF
Voir la fiche
-
The influences of the operating characteristics...
- Auteurs : XIA Y., DENG S.
- Date : 09/2016
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 69
- Formats : PDF
Voir la fiche
-
Modeling and experimental investigation of oil ...
- Auteurs : YAN Z., ZHAN F., DING G., YUE B., WU Z., ZHANG H., SHAO Y., WENG X., LI J.
- Date : 05/2024
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 161
- Formats : PDF
Voir la fiche