Document IIF

Etude expérimentale et analyse 1-D d'un éjecteur avec une tuyère primaire mobile fonctionnant avec du R236fa.

An experimental study and 1-D analysis of an ejector with a movable primary nozzle that operates with R236fa.

Auteurs : CHEN S., CHEN G., FANG L.

Type d'article : Article, Article de la RIF

Résumé

The nozzle exit position is an important structural parameter of an ejector. Research shows that movable primary nozzle enhances performance of ejectors. The present work experimentally studied the critical entrainment ratios of an ejector at different nozzle positions, finding that the critical entrainment ratio first increases with the nozzle exit position and then remains constant. A 1-D model proposed to explain this phenomenon found that in a certain range, the critical entrainment ratio is determined by choking of the secondary flow in the converging cone. When the nozzle moves upstream, the mixed flow reaches sound speed at the constant area section, and the critical entrainment ratio remains unchanged.

Documents disponibles

Format PDF

Pages : 19-25

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : An experimental study and 1-D analysis of an ejector with a movable primary nozzle that operates with R236fa.
  • Identifiant de la fiche : 30016261
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 60
  • Date d'édition : 12/2015

Liens


Voir d'autres articles du même numéro (26)
Voir la source