Etude expérimentale sur la chute de pression et les caractéristiques de transfert de chaleur local du R134a lors de la condensation dans un tube extrudé multiport.

An experimental study on pressure drop and local heat transfer characteristics of refrigerant R134a condensing in a multi-port extruded tube.

Auteurs : KOYAMA S., KUWAHARA K., NAKASHITA K., et al.

Résumé

The test rig and its monitoring devices are fully described. Experimental ranges are as follows: mass velocity of G= 100-700 kg/m2s and vapour quality of x= 1.0-0.0 at a constant inlet pressure of 1.7MPa. It is found that the experimental data of frictional pressure drop agree with the correlation of Mishima-Hibiki (1995), while the correlations of Chisholm-Laird (1958), Soliman et al. (1968) and Haraguchi et al. (1994a) overpredict. Local heat transfer data are also compared with correlations of Haraguchi et al. (1994b) and Moser et al. (1998). The data for high mass velocity agree with the correlation of Moser et al., while those for low mass velocity show different trends.

Documents disponibles

Format PDF

Pages : 2001-5

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : An experimental study on pressure drop and local heat transfer characteristics of refrigerant R134a condensing in a multi-port extruded tube.
  • Identifiant de la fiche : 2003-0670
  • Langues : Anglais
  • Source : Thermophysical Properties and Transfer Processes of New Refrigerants.
  • Date d'édition : 03/10/2001

Liens


Voir d'autres communications du même compte rendu (60)
Voir le compte rendu de la conférence