ETUDE EXPERIMENTALE SUR LA CONDENSATION DES MELANGES FRIGORIGENE-HUILE. 3. DU R12 ET DU R22 SUR LA SURFACE EXTERNE DES TUBES AILETES HORIZONTAUX UNIQUES ET MULTIPLES.

EXPERIMENTAL STUDY ON CONDENSATION OF REFRIGERANT-OIL MIXTURES. 3. R12 AND R22 ON THE EXTERNAL SURFACE OF SINGLE AND MULTIPLE HORIZONTAL FINNED TUBES.

Auteurs : WANG J. C.Y.

Résumé

ON PRESENTE LES RESULTATS D'ESSAIS RELATIFS AU R12 ET AU R22 SUR LA SURFACE EXTERNE DE TUBES AILETES HORIZONTAUX. L'HUILE UTILISEE EST A BASE D'ALKYLBENZENE. LES ESSAIS SUR LA VAPEUR DE FRIGORIGENE PUR ET CEUX SUR LES MELANGES VAPEUR-HUILE ONT ETE EFFECTUES A 305,4 ET 313,7 K (32,2 ET 40,6 DEG C). ON A OBSERVE QUE LA PRESENCE D'HUILE DANS LA VAPEUR DE R12 ET DE R22,QUEL QUE SOIT LE RAPPORT DE MASSE, ABAISSE LE COEFFICIENT DE CONDENSATION. LA DIMINUTION DU COEFFICIENT DE CONDENSATION N'EST PAS PROPORTIONNELLE AU POURCENTAGE D'HUILE POUR LES TUBES AILETES. EN CE QUI CONCERNE LA CHUTE DE PRESSION A TRAVERS LE CONDENSEUR, L'EFFET DE L'HUILE DANS LES VAPEURS DE FRIGORIGENE N'EST PAS PERCEPTIBLE.

Détails

  • Titre original : EXPERIMENTAL STUDY ON CONDENSATION OF REFRIGERANT-OIL MIXTURES. 3. R12 AND R22 ON THE EXTERNAL SURFACE OF SINGLE AND MULTIPLE HORIZONTAL FINNED TUBES.
  • Identifiant de la fiche : 1991-0608
  • Langues : Anglais
  • Date d'édition : 1989
  • Source : Source : ASHRAE Trans.
    vol. 95; n. 2; 386-392; 11 fig.; 1 tabl.; 4 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.