Etude expérimentale sur la performance du transfert de chaleur d'un refroidisseur de gaz multitubulaire au CO2.

[In Chinese. / En chinois.]

Auteurs : LÜ J., XU F., WANG J., et al.

Type d'article : Article

Résumé

The domestic and international investigations on CO2 gas cooler with different forms were summarized. The performance of three kinds of tube-in-tube gas coolers,plain tube, rectangular spiral tube and circular spiral tube were simulated. The heat transfer a-mount of unit pressure drop was put forward to evaluate the gas cooler performance in the supercritical condition. According to the simulated result,a set of tube-in-tube gas cooler with rectangular spiral tube was designed and the influences of CO2 inlet pressure,inlet water flowrate and temperature on heat transfer coefficient, heat transfer amount, COP and heat exchanger efficiency were studied experimentally. The results show that the system COP can reach 2. 85 when CO2 inlet pressure is 8 MPa, inlet water flowrate is 1.56 kg/min and inlet water temperature is 9°C. The results can provide reference for the practical application of the CO2 heat pump water heater.

Documents disponibles

Format PDF

Pages : 67-72

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails


Liens


Voir d'autres articles du même numéro (8)
Voir la source