Document IIF

Étude expérimentale sur le cycle frigorifique à absorption-diffusion utilisant des frigorigènes à faible GWP.

Experimental study on diffusion absorption refrigeration cycle using low GWP refrigerants.

Numéro : pap. n. 1107

Auteurs : JUNG H. S., KIM G., KANG Y. T.

Résumé

Compared to the conventional absorption refrigeration systems, diffusion absorption refrigeration (DAR) system consists of three components of the working fluids: refrigerant, absorbent, and auxiliary gas. In general, the DAR uses ammonia and water as the working fluids. However, ammonia is flammable, explosive, toxic, and d by high pressure gas safety management act. The main objective of this study is to select a low GWP refrigerant, its pair absorbent and auxiliary gas by experimental investigation. During the experiments, types of the refrigerant-absorbent pair, concentration of the refrigerant, pressure, and temperature are considered as the key parameters to obtain the maximum coefficient of performance (COP) and a low evaporation temperature. The optimum conditions for the key parameters were determined by experiments. It was found that R1234ze(E) gave the best COP with the evaporation temperature of -12.2 oC.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study on diffusion absorption refrigeration cycle using low GWP refrigerants.
  • Identifiant de la fiche : 30024812
  • Langues : Anglais
  • Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
  • Date d'édition : 09/2018
  • DOI : http://dx.doi.org/10.18462/iir.hfo.2018.1107