Document IIF

Etude expérimentale sur le transfert de chaleur évaporatif d'un mélange de CO2 et de diméthyléther utilisé en tant que frigorigène, à l'intérieur d'un tube lisse horizontal.

Experimental study on evaporation heat transfer of CO2/DME mixture refrigerant in a horizontal smooth tube.

Auteurs : ONAKA Y., MIYARA A., TSUBAKI K.

Type d'article : Article, Article de la RIF

Résumé

In-tube evaporation heat transfer coefficient of pure dimethyl ether (DME) and CO2/DME mixtures have been measured with water heated double tube heat exchanger under the conditions of mass flux of 100, 200, 300 kg/m2.s and inlet saturation temperature of 10°C. Test section was horizontally installed smooth tube with inner diameter of 4.2 mm. The heat transfer coefficient of mixture decreases with mixing CO2 into DME in which the degradation was about 20% for 10% CO2 and 48% for 25% CO2. Existent correlations predict the heat transfer coefficients of pure DME within plus or minus 30% error. On the other hand, heat transfer coefficient of the mixture with higher concentration 25% CO2 could not be predicted well by existent correlations, though those of 10% CO2 could be correlated fairly well.

Documents disponibles

Format PDF

Pages : pp. 1277-1291

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental study on evaporation heat transfer of CO2/DME mixture refrigerant in a horizontal smooth tube.
  • Identifiant de la fiche : 2010-1083
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 7
  • Date d'édition : 11/2010

Liens


Voir d'autres articles du même numéro (24)
Voir la source