Etude expérimentale sur les systèmes de ventilation par déplacement et par mélange pour une salle d'hôpital.

Experimental study on displacement and mixing ventilation systems for a patient ward.

Auteurs : YIN Y., XU W., GUPTA J. K., et al.

Type d'article : Article

Résumé

In hospital patient wards, exhalation flow from patients with airborne infectious diseases can impose health risks to caretakers and visitors. Usually, mixing ventilation is used to remove airborne contaminants, but displacement ventilation is becoming a popular alternative. This study investigated experimentally the performance of both mixing and displacement ventilation by using a full-scale environmental chamber to simulate a one-person patient ward. Results show that displacement ventilation may or may not provide a better air quality in the ward, depending on the location of the exhaust in relation to the restroom. A tracer gas (SF6) and 1 or 3 microm particles can be used to simulate contaminants breathed out by a patient. These contaminants generate similar contaminant distributions in the ward, except in the areas close to the contaminant source and the exhaust adjacent to the restroom, where the flow may be unstable. The experimental data obtained from this study can be used to validate the computational fluid dynamics (CFD) models.

Détails

  • Titre original : Experimental study on displacement and mixing ventilation systems for a patient ward.
  • Identifiant de la fiche : 2010-0202
  • Langues : Anglais
  • Source : HVAC&R Research - vol. 15 - n. 6
  • Date d'édition : 11/2009

Liens


Voir d'autres articles du même numéro (2)
Voir la source