Etude expérimentale sur les systèmes de ventilation par déplacement et par mélange pour une salle d'hôpital.
Experimental study on displacement and mixing ventilation systems for a patient ward.
Auteurs : YIN Y., XU W., GUPTA J. K., et al.
Type d'article : Article
Résumé
In hospital patient wards, exhalation flow from patients with airborne infectious diseases can impose health risks to caretakers and visitors. Usually, mixing ventilation is used to remove airborne contaminants, but displacement ventilation is becoming a popular alternative. This study investigated experimentally the performance of both mixing and displacement ventilation by using a full-scale environmental chamber to simulate a one-person patient ward. Results show that displacement ventilation may or may not provide a better air quality in the ward, depending on the location of the exhaust in relation to the restroom. A tracer gas (SF6) and 1 or 3 microm particles can be used to simulate contaminants breathed out by a patient. These contaminants generate similar contaminant distributions in the ward, except in the areas close to the contaminant source and the exhaust adjacent to the restroom, where the flow may be unstable. The experimental data obtained from this study can be used to validate the computational fluid dynamics (CFD) models.
Détails
- Titre original : Experimental study on displacement and mixing ventilation systems for a patient ward.
- Identifiant de la fiche : 2010-0202
- Langues : Anglais
- Source : HVAC&R Research - vol. 15 - n. 6
- Date d'édition : 11/2009
Liens
- Liens externes :
Voir d'autres articles du même numéro (2)
Voir la source
Indexation
- Thèmes : Qualité de l'air intérieur
- Mots-clés : Ventilation hybride; Contamination; Ventilation; Qualité de l'air; Hôpital; Experimentation; Conditionnement d'air
-
Prévision du profil vertical de la concentratio...
- Auteurs : SUZUKI T., SAGARA K., YAMANAKA T., et al.
- Date : 11/2008
- Langues : Japonais
- Source : Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 140
Voir la fiche
-
A study on the effect of the airflow rate of th...
- Auteurs : NOH K. C., HAN C. W., OH M. D.
- Date : 10/06/2007
- Langues : Anglais
- Source : Clima 2007. WellBeing Indoors. Proceedings of the 9th REHVA World Congress [CD-ROM + Abstract book].
Voir la fiche
-
A toolkit for aiding the design and operation o...
- Auteurs : MA X. B., CAI H., LONG W. D., et al.
- Date : 21/08/2007
- Langues : Anglais
- Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
- Formats : PDF
Voir la fiche
-
Mécanisme de la structure de l'écoulement d'air...
- Auteurs : LIM E., SAGARA K., YAMANAKA T., et al.
- Date : 12/2008
- Langues : Japonais
- Source : Transaction of the Society of Heating, Air-conditioning and Sanitary Engineers of Japan - n. 141
Voir la fiche
-
Air distribution strategy impact on operating r...
- Auteurs : SWIFT J., AVIS E., MILLARD B., et al.
- Date : 10/06/2007
- Langues : Anglais
- Source : Clima 2007. WellBeing Indoors. Proceedings of the 9th REHVA World Congress [CD-ROM + Abstract book].
Voir la fiche