Etude expérimentale sur un évaporateur à ammoniac pulvérisé avec un faisceau de tubes lisses de pas triangulaire. 2. Performance de l'évaporateur.

Experimental investigation on ammonia spray evaporator with triangular-pitch plain-tube bundle. 2. Evaporator performance.

Auteurs : ZENG X., CHYU M. C., AYUB Z. H.

Type d'article : Article

Résumé

Spray evaporation of ammonia was tested using spray nozzles distributing liquid ammonia downward onto a horizontal, 3-2-3 triangular-pitch, 1.25 pitch ratio, plain-tube bundle. The saturation temperature test range was from -23 to 10 °C, and the heat flux range from 3.2 to 35 kW/m2. The effects of heat flux, saturation temperature, spray flow rate, nozzle height, and nozzle type were investigated. Heat transfer performance was compared with other evaporator feeding systems. (See also this Bulletin, reference 2002-1271.)

Détails

  • Titre original : Experimental investigation on ammonia spray evaporator with triangular-pitch plain-tube bundle. 2. Evaporator performance.
  • Identifiant de la fiche : 2002-1257
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 44 - n. 11
  • Date d'édition : 06/2001

Liens


Voir d'autres articles du même numéro (1)
Voir la source