Experimental investigation on ammonia spray evaporator with triangular-pitch plain-tube bundle. 2. Evaporator performance.

Author(s) : ZENG X., CHYU M. C., AYUB Z. H.

Type of article: Article

Summary

Spray evaporation of ammonia was tested using spray nozzles distributing liquid ammonia downward onto a horizontal, 3-2-3 triangular-pitch, 1.25 pitch ratio, plain-tube bundle. The saturation temperature test range was from -23 to 10 °C, and the heat flux range from 3.2 to 35 kW/m2. The effects of heat flux, saturation temperature, spray flow rate, nozzle height, and nozzle type were investigated. Heat transfer performance was compared with other evaporator feeding systems. (See also this Bulletin, reference 2002-1271.)

Details

  • Original title: Experimental investigation on ammonia spray evaporator with triangular-pitch plain-tube bundle. 2. Evaporator performance.
  • Record ID : 2002-1257
  • Languages: English
  • Source: International Journal of Heat and Mass Transfer - vol. 44 - n. 11
  • Publication date: 2001/06

Links


See other articles in this issue (1)
See the source