Document IIF

Étude numérique d’un système de pompe à chaleur/refroidisseur au CO2 pour un hôtel en climat tropical.

CO2 heat pump/chiller system for a hotel in a tropical climate: a numerical investigation.

Numéro : 0261

Auteurs : ELARGA H., HAFNER A.

Résumé

The work investigates the performance of a CO2 heat-pump/chiller unit integrated with a thermal storage system to mainly provide for the domestic hot water demands of a hotel building. The thermal storage system consists of a tank holds at fully charged conditions 5m3 of hot water leaving the gas cooler at 70°C and 145 kWh of energy capacity. The heat pump’s evaporator is connected to the hotel chilled water system (12 °C to 6.5 °C) and provides a cooling capacity of 37 kW. A dynamic numerical model for the system was developed and simulation results have shown that a heat pump with a nominal heating capacity of 50 kW and a daily operation of almost 14 hours would have a COP of 6.7 and a complete system ‘s COP of 5.7 if the circulating pumps are considered. This presents an energy efficient solution if compared to a convenient boiler heating system and a separate chiller with a COP up to 3.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : CO2 heat pump/chiller system for a hotel in a tropical climate: a numerical investigation.
  • Identifiant de la fiche : 30029818
  • Langues : Anglais
  • Sujet : Technologie
  • Source : 15th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2022). Proceedings. Trondheim, Norway, June 13-15th 2022.
  • Date d'édition : 13/06/2022
  • DOI : http://dx.doi.org/10.18462/iir.gl2022.0261
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (169)