Étude numérique de comparaison des performances des méthodes de sous-refroidissement utilisant un sous-refroidisseur dans un système multi-split à débit de frigorigène variable.

Numerical study on performance comparison for sub-cooling methods using a sub-cooler in a multi-split variable refrigerant flow (VRF) system.

Numéro : pap. n. 1619

Auteurs : LEE T., MIN B., CHOI G.-M., et al.

Résumé

In this study, the performance of the VRF systems applying a bypass cycle and injection cycle using a sub-cooler is compared by numerical method. In the simulation for a multi-split variable refrigerant flow (VRF) system, it is important to predict the input power and mass flow rate of a scroll compressor with considering the refrigerant injection process in a compression chamber, and pressure drop and heat transfer in pipe lines between an outdoor unit and indoor units. Therefore, the simulation for a multi-split VRF system was developed with considering those, and validated with experimental data. The bypass and refrigerant injection have improvement potential to increase the cooling capacity due to increasing enthalpy difference in an evaporator. The refrigerant injection cycle has more improvement potential of performance than bypass cycle. Sub-cooling degree at inlet of EEV is above 10°C degree in two cycles, which can avoid flash gas generation.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Numerical study on performance comparison for sub-cooling methods using a sub-cooler in a multi-split variable refrigerant flow (VRF) system.
  • Identifiant de la fiche : 30026795
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.1619

Liens


Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence