La régulation par recherche d’extremum optimise la consommation d’énergie du système à débit de frigorigène variable.
Extremum-seeking control optimizes VRF energy consumption.
Numéro : pap. 2189
Auteurs : YANG L., WANG Y., TURNEY R. D.
Résumé
To a VRF (Variable Refrigerant Flow) system, outdoor unit (ODU) energy consumption is the combination of the power consumption of compressors and outdoor fans. The combined power consumption changes with discharge pressures and other conditions. Discharge pressures are controlled to its’ setpoint by manipulating fan speed. There are optimal discharge pressure points, where the combined power consumptions are at its’ minimum.
Most common control approaches in industry on the discharge pressure is setting them to a constant value or calculating as a function of compressor speed and ambient temperature. Fixing it to a constant value is not a desired solution since the optimal pressure points change with load, ambient temperature and other operating conditions. Calculating as a function of compressor speed and ambient temperature, though two major factors are in the consideration, still needs lab tests and calibration to find the relation between the energy consumption and discharge pressure. Since VRF system consists multiple ODUs and IDUs (Indoor Units), the task of lab tests could be overwhelming.
In this work, ESC (Extremum Seeking Control) is used to automatically find the optimum discharge/suction pressure points when VRF is in cooling/heating operation. ESC algorithm is implemented into the VRF equipment control. When ESC is enabled, a small excitement signal applies to discharge setpoint, power consumption of compressors and fans is monitored. ESC will find the optimal discharge setpoints to minimize the combined power consumption. ESC is active in all normal operation conditions, it will optimize the energy consumption over all load ranges of heating/cooling and heat recovery operation. Simulation has been conducted to demonstrate the potential savings on the outdoor unit energy consumption.
Documents disponibles
Format PDF
Pages : 10
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Extremum-seeking control optimizes VRF energy consumption.
- Identifiant de la fiche : 30024441
- Langues : Anglais
- Source : 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
- Date d'édition : 09/07/2018
Liens
Voir d'autres communications du même compte rendu (252)
Voir le compte rendu de la conférence
-
A control-oriented dynamic model of air flow in...
- Auteurs : RAISONI R., RAMAN N. S., BAROOAH P., et al.
- Date : 09/07/2018
- Langues : Anglais
- Source : 2018 Purdue Conferences. 5th International High Performance Buildings Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Model-based robust temperature control for VAV ...
- Auteurs : HUANG G., JORDAN F.
- Date : 06/2012
- Langues : Anglais
- Source : HVAC&R Research - vol. 18 - n. 3
Voir la fiche
-
Development of a virtual variable-speed compres...
- Auteurs : GUO Y., LI G., CHEN H., et al.
- Date : 02/2017
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 74
- Formats : PDF
Voir la fiche
-
Caractéristiques d'un système de conditionnemen...
- Auteurs : CAO Z.
- Date : 09/2011
- Langues : Chinois
- Source : Refrigeration - vol. 30 - n. 3
Voir la fiche
-
Generalized heuristic control for direct expans...
- Auteurs : CAI J., BRAUN J. E.
- Date : 14/07/2014
- Langues : Anglais
- Source : 2014 Purdue Conferences. 3rd International High Performance Buildings Conference at Purdue.
- Formats : PDF
Voir la fiche