Etude numérique sur les échangeurs de chaleur à tubes à ailettes et à persiennes avec des configurations de tubes circulaires et ovales.

A numerical investigation of louvered fin-and-tube heat exchangers having circular and oval tube configurations.

Auteurs : LEU J. S., LIU M. S., LIAW J. S.

Type d'article : Article

Résumé

The geometrical parameters of louver angle, louver pitch, and louver length are examined. For a fixed louver length (6.25 mm) and louver angle (14 °C), a 10% decrease of heat transfer performance is observed and a 41% decrease of pressure drop is seen for oval tube configuration. The calculated results indicate that the pressure drops always with increase in louver angle. However, an optimal value of heat transfer performance is observed due to the difference in the development of thermal boundary layer on the upper and lower louver surface. Both the heat transfer and friction performance increase with louver length. However, the rate of the increase of heat transfer performance is about the same as the increase of pressure drops.

Détails

  • Titre original : A numerical investigation of louvered fin-and-tube heat exchangers having circular and oval tube configurations.
  • Identifiant de la fiche : 2002-1762
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 44 - n. 22
  • Date d'édition : 11/2001