Résumé

In this paper, based on the homogeneous equilibrium model, the effects of nozzle inlet cross-sectional area, nozzle throat cross-sectional area, pre-mixing chamber cross-sectional area, mixing chamber cross-sectional area, and diffusion chamber outlet cross-sectional area on the performance of the ejector of a CO2 transcritical refrigeration system are analyzed by using Ansys Fluent. The simulation results show that the primary flow rate of the ejector is sensitive only to the nozzle throat cross-sectional area, while the entrainment ratio is strongly influenced by the nozzle throat and the mixing chamber cross-sectional area, and there is an optimum value. The nozzle inlet cross-sectional area has no significant effect on the performance of the ejector. The pre-mixing and diffusion chamber outlet cross-sectional areas do not have a significant effect on the performance within a limited range, but deviating too much from the optimum value can also lead to degradation of ejector performance.

Documents disponibles

Format PDF

Pages : 276-286

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Simulation study of key cross-sectional area dimensions of CO2 ejector on performance.
  • Identifiant de la fiche : 30032229
  • Langues : Anglais
  • Sujet : Technologie
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 159
  • Date d'édition : 03/2024
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2023.12.019