Document IIF
Étude sur le terrain de l’uniformité de la température de batteries disposées dans un conteneur en utilisant un système de refroidissement liquide diphasique soumis à des conditions asymétriques.
Field study on the temperature uniformity of containerized batteries using a two-phase liquid cooling system under mismatched conditions.
Résumé
The conventional liquid cooling system carries the risk of dew condensation and air cooling has poor thermal management performance for battery energy storage systems. To address these issues, a novel two-phase liquid cooling system was developed for containerized battery energy storage systems and tested in the field under mismatched conditions. The thermal management performance and safety during the charging and discharging processes were analyzed by investigating the main influencing factors, including battery temperature and cooling system characteristics (battery temperature variation, temperature uniformity, supply liquid temperature, cold plate temperature distribution, and compressor status). The results showed that the novel system can maintain a maximum cell temperature difference of less than 3 °C at the rack level and less than 2 °C at the pack level, resulting in a 60% reduction compared to the traditional air cooling system. Relative to a supply liquid temperature of 15∼25 °C, a relatively high supply temperature of 20∼30 °C for two-phase liquid cooling can not only reduce the running time of the compressor but also enhance its start-stop consistency. Compared to other studies, this novel system is reliable and safe for containerized energy storage batteries, even in capacity mismatch and direct return pipeline conditions.
Documents disponibles
Format PDF
Pages : 85-97
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Field study on the temperature uniformity of containerized batteries using a two-phase liquid cooling system under mismatched conditions.
- Identifiant de la fiche : 30033350
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 170
- Date d'édition : 02/2025
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2024.10.023
Liens
Voir d'autres articles du même numéro (37)
Voir la source
Indexation
-
A Battery Thermal Management System Coupling Hi...
- Auteurs : MO C., ZHANG G., YANG X., WU X., LI X.
- Date : 08/2022
- Langues : Anglais
- Source : Energies - vol. 15 - n. 16
- Formats : PDF
Voir la fiche
-
A Review of the Power Battery Thermal Managemen...
- Auteurs : WANG X., LIU S., ZHANG Y., LV S., NI H., DENG Y., YUAN Y.
- Date : 03/2022
- Langues : Anglais
- Source : Energies - vol. 15 - n. 6
- Formats : PDF
Voir la fiche
-
Reception of binary ice in the ice generator of...
- Auteurs : ZIMIN A. V., KHMELNIUK M., MINENKOV V.
- Date : 02/09/2013
- Langues : Anglais
- Source : Compressors 2013: 8th International Conference on Compressors and Coolants.
- Formats : PDF
Voir la fiche
-
Experimental study of the factors on solid adso...
- Auteurs : LV Y., ZHANG X.
- Date : 03/2022
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 135
- Formats : PDF
Voir la fiche
-
Particle size distribution in ice slurry system...
- Auteurs : KOFFLER M., SCHAAF J., KAUFFELD M.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche