Document IIF
Étude sur les performances thermiques dynamiques et l’optimisation de systèmes hybrides avec refroidissement par matelas capillaire et ventilation par déplacement.
Study on dynamic thermal performance and optimization of hybrid systems with capillary mat cooling and displacement ventilation.
Résumé
In this paper, the thermal performance of capillary mat cooling systems is evaluated through actual measurements under different ventilation rates. The results showed that the indoor air temperature drop rates of the ceiling, wall and floor cooling are 1.42–2.44 °C/h, 0.69–1.11 °C/h, 0.29–0.58 °C/h, respectively, in the response phase, which can provide a reference for predictive control strategy of radiant system. Then the cooling capacity of the capillary mat is validated. The radiant heat transfer coefficient of the cooling capillary mat is about 5.80 W/m 2 k. When the supply water temperature dropped from 20 °C to 16 °C, the total heat flux can experience an increase of 10%–30%. The heat flux for cooling ceilings is the largest, followed by cooling walls, which is 7%–17% lower; and cooling floors, which is 75%–90% lower. Orthogonal experiments illustrated that the water supply temperature and air supply volume have a sig- nificant influence on the indoor thermal environment of the hybrid systems, followed by the air supply temperature. In general, the dynamic performance of the radiant cooling system in the response phase can provide an effective reference for different control strategy considering the significant thermal inertia.
Documents disponibles
Format PDF
Pages : 196-207
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Study on dynamic thermal performance and optimization of hybrid systems with capillary mat cooling and displacement ventilation.
- Identifiant de la fiche : 30027300
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 110
- Date d'édition : 02/2020
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2019.10.016
Liens
Voir d'autres articles du même numéro (29)
Voir la source
Indexation
-
The optimization model of effective thermal con...
- Auteurs : ZHENG H., LIN K. T., BAE S. C., et al.
- Date : 11/07/2016
- Langues : Anglais
- Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Experimental investigation of a new combined re...
- Auteurs : GOUDARZI K., MOUSAVI M. R.
- Date : 02/2022
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 134
- Formats : PDF
Voir la fiche
-
Component-based, gray-box modeling of ductless ...
- Auteurs : CHEUNG H., BRAUN J. E.
- Date : 02/2014
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 38
- Formats : PDF
Voir la fiche
-
Radiation-enhanced thermal diode tank (RTDT) fo...
- Auteurs : WANG M., HU E., CHEN L.
- Date : 02/2023
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 146
- Formats : PDF
Voir la fiche
-
Experimental analyses of different control stra...
- Auteurs : BARTA R. B., ZIVIANI D., GROLL E. A.
- Date : 04/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 112
- Formats : PDF
Voir la fiche