Document IIF

Etude sur un nouveau refroidisseur à adsorption à gel de silice-eau. II. Etude expérimentale.

Study of a novel silica gel-water adsorption chiller. II. Experimental study.

Auteurs : WANG D. C., WU J. Y., XIA Z. Z., et al.

Type d'article : Article, Article de la RIF

Résumé

The prototype of a novel silica gel-water adsorption chiller is built and its performance is tested in detail. The experimental results show that the refrigerating capacity (RC) and COP of the chiller are 7.15 and 0.38 kW, respectively, when the hot water temperature is 84.8 °C, the cooling water temperature is 30.6 °C, and the chilled water outlet temperature is 11.7 °C. The RC will reach 6 kW under the condition of 65 °C hot water temperature, 30.5 °C cooling water temperature and 17.6 °C chilled water temperature. The results confirm that this kind of adsorption chiller is an effective refrigerating machine though its performance is not as fine as the prediction results. Also it is well effectively driven by a low-grade heat source. Therefore, its applications to the low-grade heat source are much attractive. (See also this Bulletin, reference 2005-2555.)

Documents disponibles

Format PDF

Pages : 1084-1091

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Study of a novel silica gel-water adsorption chiller. II. Experimental study.
  • Identifiant de la fiche : 2005-2558
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 28 - n. 7
  • Date d'édition : 11/2005

Liens


Voir d'autres articles du même numéro (15)
Voir la source