Résumé

This article develops an improved lump-parameter design model to investigate the water-circulation heat recovery scheme as applied to the two-bed silica gel-water adsorption chillers. The authors demonstrate that performance predictions stemming from this improved lump-parameter formalism compare favorably with experimental results at various conditions, particularly at the industrial rated conditions. They find that the present lump-parameter formalism adequately elucidates the water-circulation heat recovery scheme as does the distributed-parameter formalism. In the studied working condition of a two-bed silica gel-water adsorption chiller, the differences in cooling capacities and COPs by using the two different formalisms are typically less than 10%. This gives rise to a useful and rapid design tool for the industry.

Documents disponibles

Format PDF

Pages : 1417-1426

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Two bed silica gel-water adsorption chillers: an effectual lumped parameter model.
  • Identifiant de la fiche : 2008-0198
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 30 - n. 8
  • Date d'édition : 12/2007

Liens


Voir d'autres articles du même numéro (17)