Document IIF
Etude sur une pompe à chaleur utilisée pour chauffer de l'eau sanitaire et muni d'un système à injection de vapeur et d'un économiseur, utilisant un mélange de R22 et de R600a.
Investigation of the heat pump water heater using economizer vapour injection system and mixture of R22/R600a.
Résumé
This paper presents the experimental study of a heat pump water heater (HPWH) using economizer vapour injection system and mixture of R22/R600a. Performances of HPWH using economizer vapour injection system are compared with that at different mixed mass ratios of R22/R600a. Study demonstrates that the heating capacity and energy efficiency ratio of the unit increased, and the discharge temperature of compressor decreased when using vapour injection and mixing refrigerant of R22/R600a. It is also found that the HPWH unit with economizer vapour injection system has a better performance for the high outlet water temperature under lower temperature conditions at 15% mass ratio of R600a for the mixing refrigerant. In addition, fundamental and practical influence of vapour injection pressure on the HPWH performance has been investigated experimentally. The simplified model is proposed for predicting the optimal vapour injection pressure of compressor using the mixing refrigerant R22/R600a.
Documents disponibles
Format PDF
Pages : 509-514
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Investigation of the heat pump water heater using economizer vapour injection system and mixture of R22/R600a.
- Identifiant de la fiche : 2009-0836
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 3
- Date d'édition : 05/2009
Liens
Voir d'autres articles du même numéro (18)
Voir la source
Indexation
-
Thèmes :
Techniques des pompes à chaleur;
HCFC;
Hydrocarbures;
Mélanges - Mots-clés : Isobutane; R22; Pompe à chaleur; Performance; Injection; Experimentation; Frigorigène; Chauffage; Eau
-
Performance of propane in a unitary heat pump.
- Auteurs : HWANG Y., GADO A., RADERMACHER R.
- Date : 17/08/2003
- Langues : Anglais
- Source : 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
- Formats : PDF
Voir la fiche
-
Investigation of the potential effect of zeotro...
- Auteurs : SMIT F. J., MEYER J. P.
- Date : 1998
- Langues : Anglais
- Source : ASHRAE Transactions. 1998 Winter Meeting, San Francisco, CA.
Voir la fiche
-
Le propane en tant que frigorigène dans les pom...
- Auteurs : FREHN B.
- Date : 10/1993
- Langues : Allemand
- Source : Klima Kälte Heiz. - vol. 21 - n. 10
Voir la fiche
-
R290 in una pompa di calore: confronto con l'R2...
- Auteurs : MURA P. G., CARLINI U., INNAMORATI R.
- Date : 12/2003
- Langues : Italien
- Source : Cond. Aria - n. 11
Voir la fiche
-
Comparing R290 with R22 in heat pumps.
- Auteurs : HWANG Y., GADO A., RADERMACHER R.
- Date : 01/2003
- Langues : Anglais
- Source : ASHRAE Journal - vol. 45 - n. 1