Étude thermodynamique sur les effets des conditions d'air ambiantes sur les caractéristiques de performance thermique d'une tour de refroidissement humide.
Thermodynamic study of the effects of ambient air conditions on the thermal performance characteristics of a closed wet cooling tower.
Auteurs : PAPAEFTHIMIOU V. D., ROGDAKIS E. D., KORONAKI I. P., et al.
Type d'article : Article
Résumé
A thermodynamic model was developed and used to assess the sensitivity of thermal performance characteristics of a closed wet cooling tower to inlet air conditions. In the present study, three cases of different ambient conditions are considered: In the first case, the average mid-winter and mid-summer conditions as well as the extreme case of high temperature and relative humidity, in Athens (Greece) during summer are considered according to the Greek Regulation for Buildings Energy Performance. In the second case, the varied inlet air relative humidity while the inlet air dry bulb temperature remains constant were taken into account. In the last case, the effects on cooling tower thermal behaviour when the inlet air wet bulb temperature remains constant were examined. The proposed model is capable of predicting the variation of air thermodynamic properties, sprayed water and serpentine water temperature inside the closed wet cooling tower along its height. The reliability of simulations was tested against experimental data, which were obtained from literature. Thus, the proposed model could be used for the design of industrial and domestic applications of conventional air-conditioning systems as well as for sorption cooling systems with solid and liquid desiccants where closed wet cooling towers are used for precooling the liquid solutions. The most important result of this theoretical investigation is that the highest fall of serpentine water temperature and losses of sprayed water are observed for the lowest value of inlet wet bulb temperature. Hence, the thermal effectiveness, which is associated with the temperature reduction of serpentine water as well as the operational cost, which is related to the sprayed water loss due to evaporation, of a closed wet cooling tower depend predominantly on the degree of saturation of inlet air.
Détails
- Titre original : Thermodynamic study of the effects of ambient air conditions on the thermal performance characteristics of a closed wet cooling tower.
- Identifiant de la fiche : 30005530
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 33-34
- Date d'édition : 02/2012
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2011.09.035
Liens
Voir d'autres articles du même numéro (8)
Voir la source
-
Air cooling by evaporating droplets in the upwa...
- Auteurs : TISSOT J., BOULET P., TRINQUET F., et al.
- Date : 11/2011
- Langues : Anglais
- Source : International Journal of thermal Sciences - vol. 50 - n. 11
Voir la fiche
-
THERMAL PERFORMANCE OF SPRAY COOLING PONDS AT Z...
- Auteurs : MOUSSIOPOULOS N., ERNST G.
- Date : 02/1987
- Langues : Anglais
- Source : J. Heat Transf. - vol. 109 - n. 1
Voir la fiche
-
Characterization and performance of spray nozzl...
- Auteurs : TOGNOTTI L., ZANELLI S., BELLAGAMBA B., et al.
- Date : 07/1991
- Langues : Anglais
- Source : NIST spec. Publ. - NIST SP 813; ICLASS-91; 787-795; 8 fig.; 3 tabl.; 9 ref.
Voir la fiche
-
Experimental research of the guiding channels e...
- Auteurs : WANG K., SUN F. Z., ZHAO Y. B., et al.
- Date : 05/2010
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 30 - n. 5
Voir la fiche
-
An improved constrained inverse optimization me...
- Auteurs : SINGH K., DAS R.
- Date : 05/03/2017
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 114
Voir la fiche