Document IIF

Études expérimentales des solutions de conditionnement d'air dans des centres de données à forte densité électrique en utilisant [un modèle physique].

Experimental investigations of air conditioning solutions in high power density data centers using a scaled physical model.

Auteurs : NADA S. A., ELFEKY K. E., ATTIA A. M. A.

Type d'article : Article, Article de la RIF

Résumé

The widespread use of data centers, the dramatical increase of the data center power density and the need for improving cooling system efficiency to maintain reliable operation temperature and save cooling energy make the study of data center thermal management an urgent issue. In the current paper, three different configurations for thermal management solution of high power density data centers are investigated, compared and evaluated. A scaled physical model data center has been designed and constructed for the sake of the study using the theory of scale modeling of air flow experiments. The results showed that (i) by using aisle partition and aisle containment the rack inlet temperature can be reduced by 3–13% and 13–15.5% for aisle partition and aisle containment configurations, respectively; (ii) the intake air temperature reduction increases with increasing power density; and (iii) using aisle partitions and aisle containment with raised floor improves the data center cooling performance.

Documents disponibles

Format PDF

Pages : 87-99

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental investigations of air conditioning solutions in high power density data centers using a scaled physical model.
  • Identifiant de la fiche : 30016729
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 63
  • Date d'édition : 03/2016

Liens


Voir d'autres articles du même numéro (19)
Voir la source