Document IIF

Etudes expérimentales sur un système de refroidissement GAX modifié refroidi à l'air à absorption au NH3/H2O.

Experimental studies on air-cooled NH3-H2O based modified GAX absorption cooling system.

Auteurs : JAWAHAR C. P., SARAVANAN R.

Type d'article : Article, Article de la RIF

Résumé

An experimental investigation on the performance of an air-cooled modified generator absorber heat exchange (GAX) absorption cooling system has been carried out and presented in this paper. The conventional system is modified by incorporating high pressure GAX, low pressure GAX, a solution cooler and an additional solution heat exchanger to reduce the heat input to the system. The system is designed for a cooling capacity of 10.5 kW using ammonia-water (NH3-H2O) as the working fluid. The performance of the system in terms of the circulation ratio, internal heat recovery and COP has been obtained. The system is capable of producing a low evaporator temperature of -5°C, at a sink temperature of 35°C, under no load conditions. The results indicate that at a generator and evaporator temperature of 120 and 2°C respectively, the system delivers a maximum cooling capacity of about 9.5 kW with a fuel and total COP of 0.61 and 0.57 respectively.

Documents disponibles

Format PDF

Pages : pp. 658-666

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental studies on air-cooled NH3-H2O based modified GAX absorption cooling system.
  • Identifiant de la fiche : 2011-0129
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 3
  • Date d'édition : 05/2011

Liens


Voir d'autres articles du même numéro (20)