IIR document

Experimental studies on air-cooled NH3-H2O based modified GAX absorption cooling system.

Author(s) : JAWAHAR C. P., SARAVANAN R.

Type of article: Article, IJR article

Summary

An experimental investigation on the performance of an air-cooled modified generator absorber heat exchange (GAX) absorption cooling system has been carried out and presented in this paper. The conventional system is modified by incorporating high pressure GAX, low pressure GAX, a solution cooler and an additional solution heat exchanger to reduce the heat input to the system. The system is designed for a cooling capacity of 10.5 kW using ammonia-water (NH3-H2O) as the working fluid. The performance of the system in terms of the circulation ratio, internal heat recovery and COP has been obtained. The system is capable of producing a low evaporator temperature of -5°C, at a sink temperature of 35°C, under no load conditions. The results indicate that at a generator and evaporator temperature of 120 and 2°C respectively, the system delivers a maximum cooling capacity of about 9.5 kW with a fuel and total COP of 0.61 and 0.57 respectively.

Available documents

Format PDF

Pages: pp. 658-666

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Experimental studies on air-cooled NH3-H2O based modified GAX absorption cooling system.
  • Record ID : 2011-0129
  • Languages: English
  • Source: International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 3
  • Publication date: 2011/05

Links