Etudes sur le bruit généré par l'écoulement au niveau de l'évaporateur d'un système frigorifique.

Studies on the flow-induced noise at the evaporator of a refrigerating system.

Auteurs : CELIK S., NSOFOR E. C.

Type d'article : Article

Résumé

Studies were performed here to investigate the behaviour of flow-induced noise at the evaporator section of a refrigerating system located in an anechoic chamber. An x-ray system was used to visualize the refrigerant flow in the pertinent tubes of the system. The flow-induced noise under transient and steady-state operations of the system was studied using acoustic, pressure and temperature measurements. Calculations on the bubble size-resonant frequency and x-ray results agreed with the dominant frequency range obtained through acoustical measurements. One-third octave band analysis was performed for the 200–500 Hz frequency range as this frequency band was where the refrigerant-induced noise was found to be dominant in the system. Factors that influence the transient noise generated by the refrigerant flow were identified. [Reprinted with permission from Elsevier. Copyright, 2011].

Détails

  • Titre original : Studies on the flow-induced noise at the evaporator of a refrigerating system.
  • Identifiant de la fiche : 30005263
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 31 - n. 14-15
  • Date d'édition : 10/2011
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2011.04.014