Évaluation de frigorigènes alternatifs au R-410A dans une pompe à chaleur air-eau réversible résidentielle.

Evaluation of R-410A refrigerant alternatives in a residential reversible air-to-water heat pump.

Numéro : pap. 2103

Auteurs : PARDO P., CHARBONNIER L., MONDOT M.

Résumé

Alternative refrigerants with low-GWP are under investigation for residential heat pumps and air-conditioners as R-410A has a GWP of 2088. In this paper, two promising alternative refrigerants, DR-5A (R-454B) and L41-2 (R-447A), both HFC-HFO mixtures with a GWP of 466 and 583 respectively, were tested in a residential reversible air-to-water heat pump. The results show that R-410A replacement by L41-2 and DR-5A does not raise any particular problem and the performance obtained is, aside from some few exceptions, almost equivalent (+/-10%) to that with R-410A. These experimental results provide better understanding and knowledge about R-410A replacement in heat pumps.

Documents disponibles

Format PDF

Pages : 6

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Evaluation of R-410A refrigerant alternatives in a residential reversible air-to-water heat pump.
  • Identifiant de la fiche : 30018947
  • Langues : Anglais
  • Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 11/07/2016

Liens


Voir d'autres communications du même compte rendu (274)
Voir le compte rendu de la conférence