Évaluation de la performance d'un cycle utilisant le R448A et le R449A comme alternatives au R404A dans les systèmes frigorifiques de supermarché.
Evaluation of cycle performance of R448A and R449A as R404A replacements in supermarket refrigeration systems.
Numéro : pap. n. 563
Auteurs : MAKHNATCH P., KHODABANDEH R.
Résumé
According to the requirements of the European regulation on fluorinated greenhouse gases, refrigeration equipment that contain high Global Warming Potential (GWP) refrigerants that have GWP equal or greater than 2500, with some exceptions, will be prohibited from placing on the European market from 1st January 2020. Moreover, the use of such fluorinated greenhouse gases to service or maintain refrigeration equipment with a charge size of 40 ton of CO2 equivalent or more will be prohibited as well. The greatest impact of the Regulation in the nearest time will be therefore on users of R404A refrigerant, which is the most popular refrigerant for supermarket refrigeration systems. Equipment users and manufacturers are therefore looking for the alternative refrigerants to replace R404A in new and existing equipment. R448A and R449A are potential R404A replacements. Both are non-toxic and non-flammable refrigerant blends that closely match the properties of R404A and have GWPs significantly lower than R404A. Cycle performance of a supermarket refrigeration system, operated with R448A, R449A and R404A is modelled in this study.
Documents disponibles
Format PDF
Pages : 8 p.
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Evaluation of cycle performance of R448A and R449A as R404A replacements in supermarket refrigeration systems.
- Identifiant de la fiche : 30016371
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Date d'édition : 16/08/2015
- DOI : http://dx.doi.org/10.18462/iir.icr.2015.0563
Liens
Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence
Indexation
-
Results from supermarket system trial with R-44...
- Auteurs : GERSTEL J.
- Date : 12/06/2015
- Langues : Anglais
- Source : Le ultime tecnologie del freddo e del condizionamento. Atti del 16° Convegno Europeo: June 12-13, 2015, Milano, Italia.
- Formats : PDF
Voir la fiche
-
Nuovi refrigeranti a basso GWP alternativi al R...
- Auteurs : MINOR B., GERSTEL J.
- Date : 2013
- Langues : Italien
- Source : Industria & Formazione - vol. 37 - n. 374
- Formats : PDF
Voir la fiche
-
Non-flammable, lower GWP alternatives to R-404A.
- Auteurs : KIM S., ABBAS L., RACHED W., et al.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche
-
An evaluation of the environmental impact of di...
- Auteurs : BESHR M., AUTE V., ABDELAZIZ O., et al.
- Date : 14/07/2014
- Langues : Anglais
- Source : 2014 Purdue Conferences. 15th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Ensayos de nuevas alternativas de bajo GWP al R...
- Auteurs : MINOR B., GERSTEL J.
- Date : 09/2014
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 42 - n. 472
- Formats : PDF
Voir la fiche