Evaluation de la performance d'une pompe à chaleur à absorption-démixtion conçue pour élever le niveau de température de la chaleur à récupérer.

Evaluation of the performance of an absorption-demixtion heat pump for upgrading thermal waste.

Auteurs : NIANG M., CACHOT T., LE GOFF P.

Type d'article : Article

Résumé

The absorption/demixtion heat pump uses a partially miscible mixture as working fluid instead of a binary miscible mixture. Under low pressure the mixture is a heterogeneous solution of two non-miscible phases in thermodynamic equilibrium but at very different compositions. The solution then splits into two liquid phases without any energy supply. Beyond a critical pressure the two phases become miscible. At high temperature, the more volatile phase is evaporated and its vapour absorbed in the less volatile phase. The authors calculated the system's performance and compared its values against those of the absorption heat pump and the compression heat pump: the COP is respectively 2 and 100 times greater because the separation does not need costly energy. Moreover, the system offers investment cost savings because the separator is a simple decanter.

Détails

  • Titre original : Evaluation of the performance of an absorption-demixtion heat pump for upgrading thermal waste.
  • Identifiant de la fiche : 1999-1902
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 18 - n. 12
  • Date d'édition : 12/1998

Liens


Voir d'autres articles du même numéro (7)
Voir la source