Evaluation de la performance en régime permanent d'un échangeur d'énergie à membrane liquide-air à panneau unique (LAMEE) de petites dimensions sous conditions estivales de test définies par l'Ahri.
Evaluating the steady-state performance of a small-scale single-panel liquid-to-air membrane energy exchanger (LAMEE) under summer Ahri test conditions.
Numéro : 795
Auteurs : MOGHADDAM D. G., LEPOUDRE P., BESANT R. W., et al.
Résumé
In this paper, a novel small-scale single-panel liquid-to-air membrane energy exchanger (LAMEE) test facility has been used to experimentally investigate the effect of different number of heat transfer units (NTU) and heat capacity ratio (Cr*) on the steady-state performance of the LAMEE. The small-scale single-panel LAMEE facilitates research and development of LAMEE prototypes and the evaluation of systems design parameters without manufacturing costs and time required to build full-scale prototypes. Lithium Chloride (LiCl) is used as a salt solution in the system, and the steady-state sensible, latent and total effectiveness of the LAMEE are evaluated for two different NTUs (4.5 and 5.8), and four different Cr* values (1, 3, 5 and 7) at summer AHRI conditions, which represents the air cooling and dehumidifying test case. Moreover, a numerical code is used to numerically model the small-scale single-panel LAMEE, and numerical results are compared with experimental data. The results show that the sensible, latent and total effectiveness of the LAMEE increase with both NTU and Cr*. Maximum experimental total effectiveness of 95% is achieved for the small-scale LAMEE at NTU=5.8 and Cr*=7. Also, the agreement between the experimental data and the numerical results is acceptable, and they are within the uncertainty range of the experimental data in most cases.
Documents disponibles
Format PDF
Pages : 11 p.
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Evaluating the steady-state performance of a small-scale single-panel liquid-to-air membrane energy exchanger (LAMEE) under summer Ahri test conditions.
- Identifiant de la fiche : 30009938
- Langues : Anglais
- Source : Clima 2013. 11th REHVA World Congress and 8th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings.
- Date d'édition : 16/06/2013
Liens
Voir d'autres communications du même compte rendu (424)
Voir le compte rendu de la conférence
-
Parametric evaluation of governing heat and mas...
- Auteurs : ARMATIS P. D., FRONK B. M.
- Date : 11/07/2016
- Langues : Anglais
- Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Analysis of the factors influencing the heat ex...
- Auteurs : HU P., KANG L., WU T. H., et al.
- Date : 16/06/2013
- Langues : Anglais
- Source : Clima 2013. 11th REHVA World Congress and 8th International Conference on Indoor Air Quality, Ventilation and Energy Conservation in Buildings.
- Formats : PDF
Voir la fiche
-
Effect of environmental parameters on performan...
- Auteurs : PEGALLAPATI A. S., MADDALI R.
- Date : 27/07/2018
- Langues : Anglais
- Source : Proceedings of the International Conference on Emerging Technologies for Sustainable and Intelligent HVAC&R Systems, Kolkata, July 27-28 2018.
- Formats : PDF
Voir la fiche
-
Etude par simulation du potentiel de refroidiss...
- Auteurs : SONG L., ZHU Y.
- Date : 09/2009
- Langues : Chinois
- Source : HV & AC - vol. 39 - n. 228
- Formats : PDF
Voir la fiche
-
An analytical model for predicting frosting lim...
- Auteurs : NAVID P., NIROOMAND S., SIMONSON C. J.
- Date : 03/2019
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 99
- Formats : PDF
Voir la fiche