Évaluation des performances d’un chauffe-eau à pompe à chaleur utilisant le frigorigène de remplacement immédiat R1234yf avec modification de la taille du condenseur.

Performance evaluation on heat pump water heater with drop-in refrigerant R1234yf and condenser size modification.

Numéro : pap. n. 1686

Auteurs : SHI C., HRNJAK P.

Résumé

Refrigerant and heat exchanger design are significant factors of interest in Heat Pump Water Heater (HPWH) system. This paper presents the experimental study about R1234yf as a low global warming potential (GWP) drop-in substitute of R134a. Then condenser configuration analysis is conducted to explore the effects of condenser circuit number using the baseline R134a. It is experimentally demonstrated that the cooling capacity and COP obtained with R1234yf in a HPWH system is slightly lower than that obtained with R134a. It has been shown that R1234yf can be a desirable alternative for R134a with comparable performance but it is noted that extensive modifications should be considered if the same system performance need to be obtained. By closing the valves at the inlet and outlet of one condenser circuit, a one-circuit condenser system could be achieved. It is shown that a system operating with one-circuit condenser only brings the COP down within 5.5%.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance evaluation on heat pump water heater with drop-in refrigerant R1234yf and condenser size modification.
  • Identifiant de la fiche : 30026379
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.1686

Liens


Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence