Résumé
New refrigerants operating with a simple cycle are analysed for a wide-range critical temperatures. Considering performance, GWP (global warming potential) and flammability, R32, R452B (R32/R1234yf/R125, 67%/26%/7%) and R447B (R32/R1234zeE/R125, 68%/24%/8%) are selected for compressor performance evaluation of R410A alternatives. R32 is a single component refrigerant with excellent cycle COP (coefficient of performance) and volumetric capacity. R452B and R447B are non-azeotropic mixtures with glide from 1 to 4K, which makes refrigeration system modelling complex. Of air-cooled chiller/heat pump conditions A/B/C/D, compressor drop-in performance are compared of constant dew-point and mid-point evaporating and condensing temperatures. Mid-point condition test results show that, at condition A for R410A, R32, R452B and R447B, capacity/R410A are 100%, 106.1%, 93.3% and 86.0%, volumetric efficiency are 0.971, 0.942, 0.949, and 0.933, and power efficiency are 0.745, 0.728, 0.722, and 0.721. At condition D, discharge line temperatures are separately 93.9oC, 123.1oC, 104.2oC and 110.1oC for R410A, R32, R452B and R447B. At constant dew-point conditions, R452B and R447B show smaller capacity, and no evident power efficiency change. R410A-designed compressor shows the need to optimize efficiencies for low-GWP alternatives.
Documents disponibles
Format PDF
Pages : 7
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Performance evaluation on R410A alternatives of R32, R452B, R447B.
- Identifiant de la fiche : 30022045
- Langues : Anglais
- Source : 8th international conference on compressors and refrigeration, 2017.
- Date d'édition : 20/07/2017
Liens
Voir d'autres communications du même compte rendu (97)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Techniques des pompes à chaleur;
Compresseurs;
HFC;
Refroidisseurs d'eau - Mots-clés : Refroidisseur; R452B; R32; Substitut; Pompe à chaleur; Performance; Essai; Compresseur
-
Heating performance comparison of R410A and its...
- Auteurs : CHEN X., YANG J., LIU C., et al.
- Date : 12/2018
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 96
- Formats : PDF
Voir la fiche
-
Suitable low Global Warming Potential (GWP) ref...
- Auteurs : SHEN B., ALLY M. R., SHARMA V.
- Date : 05/2021
- Langues : Anglais
- Source : 2021 Purdue Conferences. 18th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Development of R1234ze compressor for heat pump...
- Auteurs : ZOU G., XU H., LIU T., et al.
- Date : 20/07/2017
- Langues : Anglais
- Source : 8th international conference on compressors and refrigeration, 2017.
- Formats : PDF
Voir la fiche
-
Water-source heat pumps with HFC refrigerants.
- Auteurs : GLAMM P.
- Date : 03/1995
- Langues : Anglais
- Source : IEA HPC Newsl. - vol. 13 - n. 1
Voir la fiche
-
Evaluation of performance of heat pump system u...
- Auteurs : HAIKAWA T., NUNO H., TAIRA S.
- Date : 16/08/2015
- Langues : Anglais
- Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
- Formats : PDF
Voir la fiche