Document IIF

Évaluation du système et de la fiabilité du compresseur.

Evaluation of the system and compressor reliability.

Numéro : pap. n. 917

Auteurs : TANAKA M., MATSUURA H., TAIRA S., et al.

Résumé

Recently, low global warming potential (GWP) refrigerants have attracted attention as an alternative to the most commonly used refrigerants. We considered R32 as an alternative to R410A because of its low GWP and energy saving characteristics. This study focused on the selection of a suitable refrigeration oil for R32 that would not compromise compressor reliability. We found R32 to be poorly miscible with refrigeration oils used for R410A. This, combined with a higher discharge gas temperature for R32 compared to R410A, would result in lower compressor reliability. We selected a refrigeration oil suitable for R32 and confirmed compressor reliability equivalent to R410A.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Evaluation of the system and compressor reliability.
  • Identifiant de la fiche : 30015017
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0917

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence