IIR document

Evaluation of the system and compressor reliability.

Number: pap. n. 917

Author(s) : TANAKA M., MATSUURA H., TAIRA S., et al.

Summary

Recently, low global warming potential (GWP) refrigerants have attracted attention as an alternative to the most commonly used refrigerants. We considered R32 as an alternative to R410A because of its low GWP and energy saving characteristics. This study focused on the selection of a suitable refrigeration oil for R32 that would not compromise compressor reliability. We found R32 to be poorly miscible with refrigeration oils used for R410A. This, combined with a higher discharge gas temperature for R32 compared to R410A, would result in lower compressor reliability. We selected a refrigeration oil suitable for R32 and confirmed compressor reliability equivalent to R410A.

Available documents

Format PDF

Pages: 8 p.

Available

  • Public price

    20 €

  • Member price*

    Free

* Best rate depending on membership category (see the detailed benefits of individual and corporate memberships).

Details

  • Original title: Evaluation of the system and compressor reliability.
  • Record ID : 30015017
  • Languages: English
  • Source: Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Publication date: 2015/08/16
  • DOI: http://dx.doi.org/10.18462/iir.icr.2015.0917