Document IIF

Evaluation expérimentale d'un refroidisseur à adsorption avec des dispositifs de récupération de chaleur et de masse.

Experimental testing of adsorption chiller with heat and mass recovery schemes.

Auteurs : THU K., NG K. C., SHARKAWY I. I. el-, et al.

Résumé

This paper presents the performance of a four-bed adsorption chiller using the silica-gel and water pair, operating with both heat and mass recovery schemes so as to enhance the cycle performance. The adsorption chillers have the advantage of employing low temperature waste heat which is available in abundance in the process industries. The experiments are conducted across heat source of temperatures between 65 to 85°C along with a cooling source temperature of 30°C and chilled water inlet temperature of 12.5°C. The COP of the adsorption chiller has been found up to be as high as 0.45. Employing the heat and mass recovery schemes, the optimum pressure equalization time is also determined.

Documents disponibles

Format PDF

Pages : ICR07-E1-874

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental testing of adsorption chiller with heat and mass recovery schemes.
  • Identifiant de la fiche : 2008-0643
  • Langues : Anglais
  • Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Date d'édition : 21/08/2007

Liens


Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence