Document IIF

Évaluation expérimentale d’un système au CO2 transcritique à éjecteurs multiples pour supermarchés.

Experimental evaluation of a multi-ejector trans-critical CO2 system for supermarkets.

Numéro : pap. n. 787

Auteurs : SINGH S., HAFNER A., BANASIAK K., et al.

Résumé

In the present experimental study, the performance of a multi-ejector based trans-critical CO2 cooling system is tested at high ambient temperature up to 46°C for a supermarket application with and without internal heat exchanger (IHX) and evaporative cooling. The experimental results indicate that the evaporative cooler capacity reaches a maximum at 10 cm pad thickness. However, a very marginal improvement is observed in terms of COP and PIR (Power Input Ratio) for 15 cm pad thickness. Maximum improvement in COP with IHX and evaporative cooler are 11% and 40% respectively. On the other hand, maximum reduction in the system PIR with IHX and evaporative cooler are 8.5% and 26% respectively. However, marginal enhancement in COP and PIR of 4% and 6% are observed respectively with 15 cm cooling pad thickness. From the study, it is evident that the evaporative cooling for the gas cooler of the CO2 system seems a potential solution to its application at high ambient temperature.

Documents disponibles

Format PDF

Pages : 8

Disponible

Gratuit

Détails

  • Titre original : Experimental evaluation of a multi-ejector trans-critical CO2 system for supermarkets.
  • Identifiant de la fiche : 30026212
  • Langues : Anglais
  • Sujet : Pays en développement
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.0787

Liens


Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence