Évaluation expérimentale d'une installation frigorifique au CO2 avec un système de sous-refroidissement mécanique intégré dans des conditions de fonctionnement optimales.

Experimental evaluation of CO2 refrigeration plant with integrated mechanical subcooling system at optimal working conditions.

Résumé

CO2 subcooling systems are becoming widely studied with the purpose of enhancing energy performance of the refrigeration plants in all climates. These devices increase the specific cooling capacity and reduce the optimal discharge pressure, which improves the overall COP of the system.
The integrated mechanical subcooling has a secondary compressor and only uses carbon dioxide as refrigerant. Thanks to a subcooler, placed next to the gas-cooler, it evaporates a stream of the CO2 extracted from the subcooler outlet to subcool the CO2 at the gas-cooler exit and then recompresses the evaporated CO2 until the gas-cooler entrance.
This work experimentally analyses the behaviour of a CO2 single-stage plant with integrated mechanical subcooling evaluated at different evaporation levels and different gas-cooler outlet temperatures. The system is optimized in terms of subcooling degree and discharge pressure in order to obtain the maximum COP for each operating condition.

Documents disponibles

Format PDF

Pages : 6p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental evaluation of CO2 refrigeration plant with integrated mechanical subcooling system at optimal working conditions.
  • Identifiant de la fiche : 30027910
  • Langues : Anglais
  • Sujet : Technologie, Alternatives aux HFC
  • Source : 14th IIR-Gustav Lorentzen Conference on Natural Refrigerants (GL2020). Proceedings. Kyoto, Japon, December 7-9th 2020.
  • Date d'édition : 07/12/2020
  • DOI : http://dx.doi.org/10.18462/iir.gl2020.1045
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (120)
Voir le compte rendu de la conférence