Recommandé par l'IIF / Document IIF

Évaluation semi-empirique et environnementale du frigorigène à faible PRP HCFO-1224yd(Z) en remplacement du HFC-245fa dans les pompes à chaleur à haute température.

Semi-empirical and environmental assessment of the low GWP refrigerant HCFO-1224yd(Z) to replace HFC-245fa in high temperature heat pumps.

Auteurs : MATEU-ROYO C., MOTA BABILONI A., NAVARRO-ESBRÍ J.

Type d'article : Article de la RIF

Résumé

This paper investigates a promising low-GWP refrigerant, HCFO-1224yd(Z), as an environmentally friendly replacement for HFC-245fa in high temperature heat pumps (HTHPs). First, the thermophysical properties of both fluids were analysed, and a single-stage cycle with Internal Heat Exchanger (IHX) was modelled. Then, a semi-empirical drop-in test replacement was assessed. The low-temperature reservoir was fixed at 80 °C, whereas the high-temperature reservoir was varied from 110 to 140 °C to cover a wide range of industrial applications. The theoretical and semi-empirical results illustrate that HCFO-1224yd(Z) heating capacity becomes around 8.9% lower than HFC-245fa. However, the higher suction density of HCFO-1224yd(Z) compared to the reference fluid can compensate for this effect, reducing the compressor power consumption. Hence, HCFO-1224yd(Z) presents a COP increase up to 4.5% compared to the reference fluid. At high-temperature reservoir of 140 °C, HCFO-1224yd(Z) shows a COP of 2.33, whereas HFC-245fa only reaches 2.23. The carbon footprint assessment illustrates a significant equivalent CO2,eq emissions reduction down to 90%, depending on the country (carbon emission factor). Therefore, HCFO-1224yd(Z) can be used as an alternative to HFC-245fa in HTHP systems due to its beneficial operating, energetic and environmental characteristics.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Semi-empirical and environmental assessment of the low GWP refrigerant HCFO-1224yd(Z) to replace HFC-245fa in high temperature heat pumps.
  • Identifiant de la fiche : 30028326
  • Langues : Anglais
  • Sujet : Alternatives aux HFC
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 127
  • Date d'édition : 07/2021
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2021.02.018

Liens


Voir d'autres articles du même numéro (25)
Voir la source