Expérience sur la stratification thermique dans un réservoir à accumulation thermique rectangulaire avec des diffuseurs d'eau discaux.

[In Chinese. / En chinois.]

Auteurs : ZHOU Z., XIAO R., FENG Z.

Type d'article : Article

Résumé

A chilled water storage system using discal diffusers and a rectangular storage tank was set up. Experiments in charging mode and static mode of operation were carried out at different supply and return water temperatures, and flow rates. The result shows that the thermal stratification was mainly affected by the outlet flow rate of the diffusers when the physical properties, the geometrical parameters and running conditions were almost fixed. Effective methods to control flow rate would enhance the efficiency of the storage system and the EER of the chiller. Considering the electric power price system of peak-valley value taking daily period, the storage system running in static mode could still meet the intermittent cooling requirement while the efficiency and EER would decline.

Documents disponibles

Format PDF

Pages : pp. 33-38

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails


Liens


Voir d'autres articles du même numéro (10)
Voir la source